P1 and P2 fire alarm systems: property protection explained

By FortiDraw · 4 min read · 19 Nov 2026

A P1 fire alarm system has automatic fire detection throughout all areas of a building; a P2 system has it only in defined parts of the building. Both are BS 5839-1 categories whose purpose is to protect property and the business, not people: they detect a fire early so it can be dealt with before it does serious damage.

Below: who usually asks for them, and how they combine with the life-protection categories, as in L2/P1 or M/P2.

P1 and P2 fire alarm systems in BS 5839-1

BS 5839-1, the code of practice for fire detection and alarm systems in non-domestic buildings, splits systems into three families: manual (M), life protection (L1 to L5) and property protection (P1 and P2). The Fire Industry Association's guidance on choosing a category defines the two P categories simply:

  • P1: systems installed throughout all areas of the building.
  • P2: systems installed only in defined parts of the building.

The FIA notes that a P system may well improve life safety, but its objective is protecting the property, or the business against interruption from a fire.

P1: the whole building

The FIA describes P1 as the highest level of property protection, particularly for buildings that are critical to how a company runs. Because "all areas" needs no further explanation, a P1 specification is complete on its own, in the same way as L1.

Category P1: detection throughout, to protect the property. Drawn in FortiDraw.

P2: defined areas only

A P2 specification is not complete without more detail. The FIA says it must name the rooms or areas to be protected and the type of detector in each. That list may come from a property protection or business interruption risk assessment, or it may be dictated by the property or business interruption insurer. Hyfire's pocket guide describes P2 areas as those where the risk to property or business continuity from fire is high.

Category P2: detection in defined parts of the building (here the server room, plant room and archive). Drawn in FortiDraw.

Who asks for a P category?

Usually the insurer, not the law. Fire safety legislation is about getting people out, which is what the M and L categories serve. The informative annex of BS 5839-1 that lists typical categories (summarised in FIA training material) notes that ordinary workplaces such as offices, shops, factories and warehouses often only need a Category M system to satisfy legislation, but that it is often combined with a P system to meet insurers' requirements, company policy on protecting assets, or to guard against business interruption. The same annex lists M/P1 or M/P2 for any building where detection is a requirement of a property insurer, or is fitted to earn a premium discount.

The IET's summary of the 2025 edition notes that where an enforcing authority, a property insurer or the purchaser stipulates a category, that category should be used. So if the insurance schedule says P1, that is the starting point for the design.

How P differs from L

  • Purpose. L categories protect life; P categories protect the building, its contents and the business.
  • Warning people. Apollo's guide to the standard says the main difference from an L system is that an L system needs alarm devices throughout. Safelincs notes that in a P1 system, alarm devices are only required where specified. That is one reason P categories are so often written together with M or L.
  • Getting help. The FIA's guide to BS 5839-1:2025 notes new maximum times for a fire signal to reach an alarm receiving centre: 90 seconds for Category L systems and 120 seconds for Category P systems.

For the L categories one by one, see L1, L2, L3, L4 and L5 fire alarm systems.

Combinations: L2/P1, M/P2 and more

A building often needs both life and property protection, so categories are combined with a slash, each part keeping its own meaning:

  • M/P1: Safelincs describes this as a full Category M system (call points and sounders throughout) combined with a full P1 system.
  • M/P2: a manual system plus detection in the defined high-value or high-hazard areas only.
  • L2/P1: the life-safety coverage of L2 (escape routes, rooms opening onto them and defined high-risk rooms), with the property requirement taking detection into every other area as well.
  • M/P2/L4: FIA training material gives this as a school example. M alone would satisfy the law, P2 covers valuable computer equipment, and L4 detection in the escape routes protects people using the building for evening classes.

Who decides

The FIA's guidance says the choice of category does not rest with the fire alarm designer or contractor. For P2 in particular it points to a property risk assessment or the insurer's requirements. The life-safety part of the system comes from the fire risk assessment by the responsible person. Owners should check the insurance policy and the fire risk assessment before asking for quotes; installers should make the proposed category clear before the order is placed. The broader picture is in commercial fire alarm categories and who chooses one.

Drawing a P2 system

Because P2 depends on which rooms are in, a marked-up plan is the clearest specification. In FortiDraw's fire alarm page you place detector symbols in the protected rooms and draw zones that number themselves Z01, Z02 and so on; our fire alarm layout guide shows the steps.

Mark up a fire alarm plan free at FortiDraw.


General information, checked in November 2026, not advice for your premises. Definitions follow the Fire Industry Association's guidance on BS 5839-1 and manufacturers' guides; check the current edition of the standard, your insurer's requirements and your fire risk assessment. See GOV.UK: fire safety in the workplace.

More on Fire safety

Fire alarm grades explained: A, C, D1, D2, F1 and F2Fire alarm grades describe the kind of system in a home. The six grades in BS 5839-6:2019+A1:2020, how a grade differs from a category such as LD2, and which grade is recommended where.Fire safety · 5 min · 19 Nov 2026Fire alarm system categories explained: M, L1–L5, P1, P2 and LD1–LD3Every UK fire alarm system category on one page: M, L1 to L5, P1 and P2 from BS 5839-1, and LD1 to LD3 from BS 5839-6 for homes, each in a sentence or two, with a diagram and links to the detailed guides.Fire safety · 4 min · 19 Nov 2026L1 fire alarm system requirements: what whole-building cover meansAn L1 fire alarm system has automatic detection throughout the building. The L1 definition, the low-risk areas BS 5839-1 lets you leave out, what changed in 2025, and when L1 is specified.Fire safety · 3 min · 19 Nov 2026