Fire alarm system categories explained: M, L1–L5, P1, P2 and LD1–LD3

By FortiDraw · 4 min read · 19 Nov 2026

Fire alarm system categories say what a system is for and how much of the building it covers. In the UK they come from two British Standards: BS 5839-1 for non-domestic buildings (categories M, L1 to L5, P1 and P2) and BS 5839-6 for homes (LD1, LD2, LD3, plus PD1 and PD2).

This page puts every category on one page, a sentence or two each, with links to the detailed guides. A category on its own is never the whole specification: several need a list of rooms, and homes also need a grade.

Fire alarm system categories in BS 5839-1 (non-domestic)

The Fire Industry Association's guidance says BS 5839-1 defines eight categories, depending on whether the system is manual or automatic and, if automatic, what the detection is for and how far it extends. BS 5839-1:2025, which the IET notes came into effect on 30 April 2025, keeps the same families; the FIA's guide to it describes changes within L2, L3 and L4 rather than new categories.

M: manual

Manual call points and sounders, no automatic detectors. Generally enough to satisfy fire safety law in workplaces where nobody sleeps.

Category M: call points at the exits, no detectors. Drawn in FortiDraw.

L: automatic detection to protect life

  • L1: detection throughout all areas of the building, apart from a few low-risk spaces. See L1 fire alarm system requirements.
  • L2: everything in L3, plus defined rooms where a fire is especially likely or would put lives at high risk. Since the 2025 edition, rooms where people sleep count as high-risk rooms.
  • L3: the escape routes and the rooms that open onto them, so people can escape before smoke makes the routes impassable.
  • L4: the circulation areas of the escape routes only, such as corridors and stairways. See L4 fire alarm systems.
  • L5: bespoke detection to meet one specific fire safety objective that L1 to L4 don't, such as releasing fire doors or warning someone in an inner room.

All five are compared in more depth in L1, L2, L3, L4 and L5 fire alarm systems.

Category L1: detection throughout the building. Drawn in FortiDraw.

Category L2: L3 plus defined high-risk rooms (here the store). Drawn in FortiDraw.

Category L3: escape routes and the rooms that open onto them. Drawn in FortiDraw.

Category L4: the escape routes only. Drawn in FortiDraw.

Category L5: detection where a defined objective needs it (here the server room). Drawn in FortiDraw.

P: automatic detection to protect property

  • P1: detection throughout the building.
  • P2: detection only in defined parts of the building.

P categories protect the building and the business, and are usually asked for by insurers. See P1 and P2 property protection.

Category P1: detection throughout, to protect the property. Drawn in FortiDraw.

Category P2: detection in defined parts of the building (here the server room, plant room and archive). Drawn in FortiDraw.

Combinations

Categories can be combined, written with a slash: M/L5 (a manual system with a little targeted detection), M/P2, or L2/P1 when both life and property need protecting. The FIA's training material even gives a school example of M/P2/L4.

Categories in BS 5839-6 (homes)

Homes use a separate part of the standard, and its categories carry a D for domestic:

  • LD1: alarms in all areas where a fire could start, including bedrooms, as well as the escape route.
  • LD2: the escape route plus higher-risk rooms, typically the kitchen and the main living room.
  • LD3: the escape route only: hallways and landings.
  • PD1 and PD2: property protection throughout, or in defined areas.

Room by room detail is in LD1, LD2 and LD3 fire alarm systems in homes.

Categories and grades

BS 5839-6 adds a second label, the grade (A, C, D1, D2, F1, F2), which says what kind of equipment the system uses and how it is powered. A home's system is specified as both, such as "Grade D1 Category LD2". Non-domestic systems under BS 5839-1 have categories only. See fire alarm grades explained.

What needs more than the category

The FIA points out that only M, L1, P1 and L4 are complete on their own. The others need extra information:

  • L2: which extra rooms, and the detector type.
  • L3: the detector type in the rooms off the escape routes.
  • L5 and P2: which areas are protected, and with which detector types.

Who decides the category

Not the installer alone. For non-domestic buildings, the FIA's guidance says the category comes from the fire safety side (the responsible person's fire risk assessment, a fire safety consultant, building control or the enforcing authority), with insurers able to set property requirements. For homes, building regulations, landlord rules and the council's HMO standards set the minimum. The installer's job is to design to the category and make it clear before work starts. More in commercial fire alarm categories and who chooses one.

Showing the category on a drawing

The rooms in and out are easiest to agree on a plan. In FortiDraw you place detectors and call points on a fire alarm page and draw zones numbered Z01, Z02… for the zone chart; see fire alarm layout drawings.

Try FortiDraw free.


General information, checked in November 2026, not advice for your premises. Based on the Fire Industry Association's guidance on BS 5839-1 and manufacturers' guides to BS 5839-6; check the current standards and your fire risk assessment. See GOV.UK: fire safety in the workplace.

More on Fire safety

Fire alarm grades explained: A, C, D1, D2, F1 and F2Fire alarm grades describe the kind of system in a home. The six grades in BS 5839-6:2019+A1:2020, how a grade differs from a category such as LD2, and which grade is recommended where.Fire safety · 5 min · 19 Nov 2026L1 fire alarm system requirements: what whole-building cover meansAn L1 fire alarm system has automatic detection throughout the building. The L1 definition, the low-risk areas BS 5839-1 lets you leave out, what changed in 2025, and when L1 is specified.Fire safety · 3 min · 19 Nov 2026L4 fire alarm system: detection in the escape routes onlyAn L4 fire alarm system puts automatic detection only in escape routes such as corridors and stairways. Where it is used, what it leaves out, the 2025 change, and how it compares with L3 and L5.Fire safety · 4 min · 19 Nov 2026